Attic Ventilation Calculator

Enter the insulated ceiling area of the attic and the roof slope and get the unobstructed vent area at the ratio the National Building Code of Canada 2020 prints for that slope, with the number of vents if you enter the area of one vent. The working is shown for an example.

Estimates for planning, not professional advice. Read the full notice.

Attic

Like 11 m²

reads as 100 square metres, 1,076.39 square feet

Like 11 m²

Example: an attic under a roof that slopes 1 in 6 or more

3,333.33 cm² (3.59 ft²)

  • Vent area at the ratio for a slope less than 1 in 6 6,667 cm² (7 ft²)

Estimate for planning, from what you entered and the product data shown. Check product labels and your supplier before you buy.

Share this project

This link carries:

    The project is inside the link, after the # sign. Browsers do not send that part to the site.

    Questions

    How much attic vent area do I need?

    Divide the insulated ceiling area by the ratio the code prints for your roof slope. The first table gives the result at both ratios for a range of ceiling areas, and the example shows the working.

    Where do the ratios come from?

    They are quoted from Sentence 9.19.1.2.(1) of the National Building Code of Canada 2020, which the National Research Council publishes free of charge. Each province and territory adopts the model code with its own changes, so your local building department decides what applies.

    How many vents do I need?

    Enter the unobstructed area printed for one of your vents, and the count is the vent area over it, rounded up once. Check the label or ask your supplier for that figure.

    Worked example: an attic under a roof that slopes 1 in 6 or more

    Show the steps
    1. Vent area: the ceiling area over the ratio for a slope of 1 in 6 or more 100 m² (1,076.39 ft²) ÷ 300 = 3,333 cm² (4 ft²)
    2. For a slope less than 1 in 6 or roof joists: the ceiling area over that ratio 100 m² (1,076.39 ft²) ÷ 150 = 6,667 cm² (7 ft²)

    Assumptions

    The figures behind the example. Sourced figures link to their source below; a default is a starting value to check against your label or supplier.

    AssumptionValueDetails and changes
    Ceiling area for each unit of vent area, roof slope 1 in 6 or more 300[1]
    NBC 2020 Sentence 9.19.1.2.(1) gives the unobstructed vent area of an attic as not less than 1/300 of the insulated ceiling area, and 1/150 where the roof slope is less than 1 in 6 or on roof joists.
    Ceiling area for each unit of vent area, roof slope less than 1 in 6 or roof joists 150[1]
    NBC 2020 Sentence 9.19.1.2.(1) gives the unobstructed vent area of an attic as not less than 1/300 of the insulated ceiling area, and 1/150 where the roof slope is less than 1 in 6 or on roof joists.

    Vent area by insulated ceiling area

    Unobstructed vent area at each NBC ratio, by insulated ceiling area

    Unobstructed vent area at each NBC ratio, by insulated ceiling area
    Insulated ceiling areaSlope 1 in 6 or moreSlope less than 1 in 6, or roof joists
    50 m² (538.2 ft²) 1,667 cm² (2 ft²)3,333 cm² (4 ft²)
    75 m² (807.29 ft²) 2,500 cm² (3 ft²)5,000 cm² (5 ft²)
    100 m² (1,076.39 ft²) 3,333 cm² (4 ft²)6,667 cm² (7 ft²)
    150 m² (1,614.59 ft²) 5,000 cm² (5 ft²)10,000 cm² (11 ft²)
    200 m² (2,152.78 ft²) 6,667 cm² (7 ft²)13,333 cm² (14 ft²)

    Each row is worked out on its own at the two ratios the code prints.

    What NBC 2020 prints for attic vent area

    The ratios of Sentence 9.19.1.2.(1) of the National Building Code of Canada 2020, Part 9

    The ratios of Sentence 9.19.1.2.(1) of the National Building Code of Canada 2020, Part 9
    FigureValue in the code
    Ceiling area for each unit of vent area, roof slope 1 in 6 or more 300
    Ceiling area for each unit of vent area, roof slope less than 1 in 6 or roof joists 150

    Source: [1]

    These are model-code figures. Provinces and territories adopt the code with changes, and the code adds where the vents go: your local building department decides what applies to your attic.

    Sources (1)

    1. National Building Code of Canada 2020, Sentence 9.19.1.2.(1), page 9-109 (opens in new tab), National Research Council of Canada, NBC 2020, Division B (Volume 2), NRC printing with revisions and errata of 31 March 2025. Code or government.
      “unobstructed vent area shall be not less than 1/300 of the insulated ceiling area.”
      “1/150”
      Checked 13 November 2026. Figures and codes change; verify with the source. Back to where this is used (Source 1)

    These are summaries of what the sources say, not professional advice. Building codes and product data change. Check with your local building department and the product label about your own project.